1 FUNCTIONS
1.7 Input Signal Error Detection Function
45
1
The following figure shows the operation of the input signal error detection.
21.2mA
20mA
4mA
1.2mA
3.6mA
16mA
0.4mA
Input signal error detection
upper limit value
Gain value
Lower limit value of input
range (offset value)
Input signal error detection
lower limit value
Error
detected
Error
detected
(7.5% of 16mA)
(22.5% of 16mA)
(Gain value - Offset value)