EasyManua.ls Logo

Nailor 35SW - Damper Operation; Fan Operation

Default Icon
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IOM-EZVAVINST
Date: 10-2016 Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Page 38 of 48
Installation and Operation Manual
EZvav Digital Controls
DamperOperaon
Damper movement is determined by comparing the actual airow reading to the airow set points. If the actual airow is within
5% of the set point, no damper acon is iniated. Once within the 5% deadband, the actual airow must be outside a 7% deadband
before damper posion changes.
FanOperaon
The EZvav controllers support both series and parallel fan powered VAV units. For either type of fan operaon, the fan is controlled
through the following terminals.
A binary output triac controls a 24-volt fan starng circuit. See the topic Conguring the VAV Terminal Unit opons on
page 17 for the procedure to congure the controller for a fan.
A 0-10 volt DC analog output controls the speed of the fan. The output controls fan speed at either Min Fan Speed or Max
Fan Speed. See the topic Set the airow set points on page 19 for the procedure to set the fan speeds.
If the VAV unit is not congured for a fan, the two outputs are not used and remain inacve regardless of the occupancy state.
SeriesFan
If the controller is congured for a series fan, any me the Occupancy mode of the controller is set to either Occupied or Standby,
the fan runs connuously. The fan speed is set to Maximum Fan Speed when the state is Occupied and set to Minimum Fan Speed
when the state is Standby.
When the Occupancy state is Unoccupied, the fan starts and runs at minimum speed only on a call for heang. The fan starts when
the Heang loop is greater than 5% and stops when the Heang loop is less than 1%.
Figure8-2 Seriesfanoperaon
ParallelFan
If the controller is congured for a parallel fan, any me the Occupancy mode of the controller is set to either Occupied or Standby
and there is a call for heat, the fan runs connuously. The fan starts when the Heang loop is greater than 5% and stops when the
Heang loop is less than 1%.
When the unit Occupancy state is Unoccupied, the fan starts and runs at minimum speed only on a call for heang. The fan starts
when the Heang loop is greater than 5% and stops when the Heang loop is less than 1%.
Figure8-3 Parallelfanoperaon
UNOCCUPIED/
STANDBY
STANDBY
MAX FAN SPEED
MIN FAN SPEED
FAN OFF
OCCUPIED
HTG SP ROOM TEMP INCREASE
MAX FAN SPEED
MIN FAN SPEED
FAN OFF
OCCUPIED
HTG SP ROOM TEMP INCREASE
UNOCCUPIED/
STANDBY

Table of Contents