Installation and Operation Manual
EZvav Digital Controls
Proceduretosettheadvancedopons(connue)
RestoreApplicaon
Choose the RSTR funcon to reset the EZvav controller to the original conguraon and sengs. Use it also to change the units of
measure to display on a EZvav sensor. There are two versions of the applicaon program in the controller.
The Metric version displays temperature in Celsius and uses metric values for units of measure.
The English version displays temperature in Fahrenheit and uses English values for units of measure.
Access to the Restore Applicaon funcon requires entering Password 2 which is described in the topic Geng started with
conguraon on page 14.
Tip: Once the following procedure is started, all steps must be completed in order.
Proceduretorestoreapplicaon
CAUTION Choosing RSTR deletes all previously
congured values including balancing values and
passwords. Only the BACnet communicaons
sengs will remain unchanged.
PROCEDURE STEPS STEDISPLAY
1 Starng display
1. Start at the temperature display.
2. Press the
and buons together.
If Password 2 is not required, the display changes to
CNFG.
If required, enter Password 2. The display changes to
CNFG when Password 2 is correct.




PROCEDURE STEPS STEDISPLAY
8 Set the temperature sensor
calibraon constant.
1. Press the
or buons to set the calibraon
constant. The set point will change in 0.1 minute
increments.
For a low input reading enter a posive correcon
value.
For a high input reading enter a negave correcon
value.
2. Press the
buon to save the set point and
advance to the next funcon.


9 Select a new conguraon
funcon or exit.
1. Press the
or buons to select one of the
following:
STPT, FLOW, BOX, or RSTR opons
BACK to choose .another conguraon funcon
EXIT to return to the temperature display.
2. Press the buon to select the next funcon.
