EZvav Digital Controls
Proceduretosettheadvancedopons(connue)
RestoreApplicaon
Choose the RSTR funcon to reset the EZvav controller to the original conguraon and sengs. Use it also to change the units of
measure to display on a EZvav sensor. There are two versions of the applicaon program in the controller.
• The Metric version displays temperature in Celsius and uses metric values for units of measure.
• The English version displays temperature in Fahrenheit and uses English values for units of measure.
Access to the Restore Applicaon funcon requires entering Password 2 which is described in the topic Geng started with
conguraon on page 14.
Tip: Once the following procedure is started, all steps must be completed in order.
Proceduretorestoreapplicaon
CAUTION Choosing RSTR deletes all previously
congured values including balancing values and
passwords. Only the BACnet communicaons
sengs will remain unchanged.
PROCEDURE STEPS STEDISPLAY
1 Starng display
1. Start at the temperature display.
2. Press the
∆
and buons together.
• If Password 2 is not required, the display changes to
CNFG.
• If required, enter Password 2. The display changes to
CNFG when Password 2 is correct.
∆
PROCEDURE STEPS STEDISPLAY
8 Set the temperature sensor
calibraon constant.
1. Press the
∆
or buons to set the calibraon
constant. The set point will change in 0.1 minute
increments.
• For a low input reading enter a posive correcon
value.
• For a high input reading enter a negave correcon
value.
2. Press the
buon to save the set point and
advance to the next funcon.
9 Select a new conguraon
funcon or exit.
1. Press the
∆
or buons to select one of the
following:
• STPT, FLOW, BOX, or RSTR opons
• BACK to choose .another conguraon funcon
• EXIT to return to the temperature display.
2. Press the buon to select the next funcon.
∆
∆