Installation and Operation Manual
●
EZvav Digital Controls
ReheatSequence
The EZvav controllers can control three types of reheat installaons.
• Modulang reheat
• Staged reheat
• Floang reheat
All reheat is controlled by either the Heang loop or the Discharge Air Temp Liming (DAT) PID loop. Loops are described in the
topic PID control loops on page 36.
• If Discharge Air Temp Liming is enabled, reheat is controlled by the DAT PID loop.
• If DAT control is not enabled, reheat is controlled by the Heang loop.
In the following descripons, the loop controlling reheat is referred to as the Reheat loop.
Modulangreheat
If the controller is congured for modulang reheat, it controls an analog reheat unit with 0-10 volts DC at the analog reheat
output. On a call for reheat, the reheat output is modulated over the span of the Reheat loop. If the Reheat loop is less than 10%,
the reheat output remains at zero. The reheat is set to zero if the Cooling loop is acve.
See the topic Modulang reheat on page 31 for an applicaon drawing.
Figure8-4 Modulangreheatoperaon
Stagedreheat
If the controller is congured for staged reheat, it can control up to three stages of reheat through binary triac outputs. The reheat
outputs are commanded On when the Reheat loop rises above the On threshold and O when the loop drops below the O
threshold. Thresholds are described in the following chart, Staged reheat thresholds on page 39.
See the topic Staged reheat on page 30 for an applicaon drawing.
Table8–1 Stagedreheatthresholds
HeangStage
OutputState
Onthreshold Othreshold
Stage 1 35% 15%
Stage 2 65% 45%
Stage 3 95% 75%
Room temp increase
HTG SPAN
loop %
0
100
10
HTG %