Installation and Operation Manual
●
EZvav Digital Controls
Proceduretosetthetemperaturesetpoints(connue)
ConguringtheVAVTerminalUnitOpons
The unit opons set the controller for the specic mechanical installaon of the VAV terminal unit. The unit opons include the
following items.
• The K-factor for the VAV terminal unit. If the K-factor is not available, see the topic K-factors on page 47.
• Reheat conguraon (oponal)
• Fan conguraon (oponal)
• Direcon of damper to close
Seng the unit opons requires entering Password 2 which is described in the topic Geng started with conguraon on page 14.
Tip: Once the following procedure is started, all steps must be completed in order.
ProceduretosettheTerminalUnitfuncons
PROCEDURE STEPS STEDISPLAY
11 Set the standby dierenal set
point.
The standby set point is calculated by adding or
subtracng the oset value to or from the value of the
occupied set point.
1. Press the
∆
or
buons to set the standby
dierenal set point. The set point will change in 1°
increments.
2. Press the buon to save the set point and
advance to the next funcon.
12 Select a new conguraon
funcon or exit.
1. Press the
∆
or
buons to select one of the
following:
•
BOX, FLOW, ADVC, or RSTR opons
•
BACK to choose another conguraon
funcon.
•
EXIT to return to the temperature display.
2. Press the buon to select the next funcon.
PROCEDURE STEPS STEDISPLAY
1 Starng display
1. Start at the temperature display.
2. Press the
∆
and buons together.
• If Password 2 is not required, the display changes to
CNFG.
• If required, enter Password 2. The display changes to
CNFG when Password 2 is correct.
∆
∆
∆