EasyManua.ls Logo

Nailor 35SW - Connecting A Dat Sensor; Connecting Power; Connecting a DAT Sensor; Maintenance

Default Icon
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IOM-EZVAVINST
Date: 10-2016 Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Page 10 of 48
Installation and Operation Manual
EZvav Digital Controls
ConnecngaDATSensor
The Discharge Air Temperature sensor is required for automac changeover and for VAV terminal units with reheat.
Figure2-5 Dischargeairtemperaturesensorlocaon
Connect a 10 kΩ, Type 3 thermistor temperature probe to the discharge air temperature input. The input includes the internal
pull-up resistor. An STE-1401 sensor is suitable for this applicaon. Follow the instrucons supplied with the sensor for installaon,
or refer to pages 11-12 for this informaon.
For DAT liming and reheat, install the sensor in the airow aer the reheat secon. See the topic, Advanced opons on
page 21 to enable discharge air temperature control.
When the DAT sensor is used only to detect primary air temperature, the sensor can be placed in either locaon shown in
the Figure Discharge air temperature sensor locaon.
Figure2-6 Dischargeairtemperatureinputdetails
ConnecngPower
The controllers require a 24 volt, AC power source. Use the following guidelines when choosing and wiring transformers to the
controller.
A Class – 2 transformer is supplied with each unit.
Connect the 24 volt AC power supply to the power terminal block on the lower right side of the controller. Connect the ground
side of the transformer to the ground terminal and the AC phase to the phase terminal. Power is applied to the controller when
the transformer is connected to power.
Figure2-7 Controllerpowerterminals
Maintenance
Nailor EZvav controllers require no roune maintenance. If necessary, clean with a damp cloth and mild soap.
T
COMM
READY
AI1
GND
AO4
AO3
24 VAC
Class 2
ON CTS
1 2
COMM
READY
AI1
AI5
GND
AO4
AO3
SC
BO8
BO5
BO6
SC
BO7
24VAC
AI6
GND
AI7
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
DAT sensor
Preferred location
DAT sensor
Changeover only

Table of Contents