29
2-2. Specifications
2-2. Specifications
1. General Specifications
Ambient temperature
Ambient humidity
Storage temperature
Storage humidity
Breakdown voltage
Insulation resistance
Vibration resistance
Shock resistance
Noise immunity
Operating condition
Rated
operating
voltage
Operating
voltage range
0˚C to +55˚C/32˚F to +131˚F
30 % to 85 % RH (non-condensing)
–20˚C to +70˚C/–4˚F to +158˚F
30 % to 85 % RH (non-condensing)
AC type: 1,500 Vrms for 1 min
Between AC terminal and Frame ground terminal
DC type: 500 Vrms for 1 min
Between DC terminal and Frame ground terminal
Min. 100 M (measured with a 500 V DC megger)
Between AC terminal and Frame ground terminal
Between DC terminal and Frame ground terminal
10 Hz to 55 Hz, 1 cycle/min: double amplitude of 0.75 mm/0.030 in., 10 min on 3 axes
Shock of 98 m/s
2
or more, 4 times on 3 axes
1,000 Vp-p with pulse widths 50 ns and 1 µs (based on in-house measurements)
Free from corrosive gases and excessive dust
AC type: 100 V to 240 V AC
DC type: 24 V DC
AC type: 85 V to 264 V AC
DC type: 20.4 V to 26.4 V DC
Control Unit
(all series)
Expansion Unit
(E24 and E40
series only)
FP1 A/D
Converter Unit
FP1 D/A
Converter Unit
FP1 Transmitter
Master Unit
FP1 I/O
Link Unit
Control Unit
(all series)
Expansion Unit
(E24 and E40
series only)
FP1 A/D
Converter Unit
FP1 D/A
Converter Unit
FP1 Transmitter
Master Unit
FP1 I/O
Link Unit