2-2. Specifications
Triac output type
L
Internal
circuit
"
"
"
Output
terminals
L
COM
L: Load
(FP1 Expansion Unit)
Wiring diagram
~
LED
Insulation method
Output type
Rated load voltage range
Operating load voltage range
Max. load current
Min. load current
Max. surge current
OFF state leakage current
ON state voltage drop
Response time
Surge absorber
Operating mode indicator
Connection method
Optical coupler
Triac
100 V to 240 V AC
85 V to 250 V AC
1 A/point, 1 A/common
30 mA
15 A, 100 ms or less
4 mA or less (at 240 V AC)
1.5 V or less (at 0.3 A to 1 A load),
5 V or less (at 0.3 A or less load)
1 ms or less
0.5 cycle + 1 ms or less
Varister
LED
Terminal block (M3.5 screw)
OFF ON
ON OFF