Scenarios:
• Time is 10:00, the measured temperature is 35
o
C and the measured relative humidity is 65%, the cooling
valve will be open for 30 seconds and close for 2:00 minutes in a continuous cycle.
• Time is 12:00, the measured temperature is 30
o
C and the measured relative humidity is 65%, the cooling
valve will be open for 30 seconds and close for 3:00 minutes in a continuous cycle.
• Time is 14:00, the measured temperature is 40
o
C and the measured relative humidity is 50%, the cooling
valve will be open for 30 seconds and close for 1:00 minutes in a continuous cycle.
• Time is 15:00, the measured temperature is 35
o
C and the measured relative humidity is 85%, the cooling
valve will not be open since the measured relative humidity is above the maximum allowed (80%).
Note: If more than one cooling valve is def
i
ned, the off time will take place after the last valve in the sequence
(Cooling valve #2, in the above screen). Between the cooling valves there is no delay and they are working in
sequence, from the first valve on the left side to the last one.
Note: If the time is relevant only for a certain period, only its settings will define operation. If humidity is above
the lowest value of the two periods, cooling will not take place.
• From (hh:mm): Set the start time of the Cooling / Humidification program.
• To (hh:mm): Set the end time of the Cooling / Humidification program
Note: The program will only be operational in the defined time window (between start “From” to end “To” times).
Each program can be operational on different hours.
• Above t
o
/ Below RH
Above t
o
(when status is cooling): Start cooling above this temperature. Cooling will stop if the
temperature drops below the internal dead-band of 0.5
o
C. For example if set to 30
o
C cooling will start
when the temperature is above 30
o
C and will stop when it drops below 29.5
o
C. °
Below RH (when status is humidification): Start humidification below this humidity. Humidification will
stop if the humidity goes above the internal dead-band of 1%. For example, if set to 80% humidification
will start when the humidity is below 80% and will stop when it is above 81%.
• Below RH / Above t
o
Below RH (when status is cooling): Stop cooling above this humidity. Cooling will be resumed when
the humidity drops below the internal dead-band of 2%. For example, if set to 80% cooling will stop
when the humidity is above 82% and will be resumed when the humidity drops below 80%.
Above t
o
(when status is humidification): Stop humidification when the temperature is below this
temperature. Humidification will be resumed when the temperature goes above the internal dead-band
of 0.5
o
C. For example, if set to 25
o
C humidification will stop when the temperature drops below 24.5
o
C
and will be resumed when it goes above 25
o
C.