EasyManua.ls Logo

Nibe FIGHTER 1110 - Power Connection and Sensor Installation

Nibe FIGHTER 1110
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The outside sensor (15) must be installed in a
shaded location on a wall facing north or north-
west, where it will not be affected by any morning
sun. The sensor is connected by two wires to ter-
minals 7 and 8 of terminal block 30 on the relay
card (29). The minimum cable cross section is 0.4
mm
2
up to 50 metres. Suitable cable types are
EKKX or LiYY.
If the outside temperature sensor cable runs close
to power cables, screened cable should be used. If
a conduit is used it must be sealed to prevent con-
densation in the sensor capsule.
The outdoor sensor should be connected, e.g. to
the heat pump with fixed condensing.
Electrical connection 21
For the Installer
FIGHTER 1110
SELV
+BAB+ A
RTG EXT.EL.UG
15
12345678
30
A heat pump must not be connected without the
permission of the electricity supplier and must be
connected under the supervision of a qualified
electrician.
If an automatic fuse unit is used this should have a
motor characteristic D (compressor operation). For
MCB size see Technical Specifications.
The FIGHTER 1110 does not include an isolator
switch on the incoming electrical supply. Therefore
the installation must be preceded by a circuit-
breaker.
If an insulation test is to be carried out in the build-
ing, disconnect the heat pump.
Connect the heat pump to 400 V 3-phase, neutral +
ground via a distribution board with fuses. Does not
apply to FIGHTER 1110-4 kW without electrical
supplement, where 230V 1-phase + ground is suffi-
cient.
Connect an external, potential free make contact to
terminal (30) pos 1 and 2 to disconnect the entire
electrical output.
Connect an external, potential free make contact to
terminals 1 and 3 on terminal block (30) to discon-
nect the entire electrical output, but with the possi-
bility to use Extra hot water during the period with-
out output.
Connect the load monitor EBV 200 (accessories) to
terminal (30) pos 1 and 2 to disconnect the electri-
cal output in steps.
Disconnection of the entire electrical power is
achieved by connecting an external potential-free
make (NO) contact to terminal (30) pos 1. and 2
together with pos 3 (pos 2 and 3 are connected
together).
Connection
Connecting the outside sensor
External control of the immersion heater
NOTE!
A 1-phase connection without
electrical supplement requires pos L1
and L3 to be strapped on terminal (9).
LEK
+2
-2
1
R
0
30

Table of Contents

Related product manuals