System Design
NEMA motor ratings
All ratings are calculated at altitude of 1000 metres and ambient temperature of 50 ºC.
Light
300%, 10 s,
6 starts per hour
Normal
350%, 30 s,
4 starts per hour
Heavy
450%, 30 s,
4 starts per hour
A
HP
@240
VAC
HP
@480
VAC
HP
@600
VAC
A
HP
@240
VAC
HP
@480
VAC
HP
@600
VAC
A
HP
@240
VAC
HP
@480
VAC
HP
@600
VAC
0024B
24
7.5
15
20
17
5
10
15
14
3
10
10
0042B
42
15
30
40
28
10
20
25
22
7.5
15
20
0052B
52
15
30
50
35
10
25
30
28
10
20
25
0064B
64
20
40
60
52
15
40
40
40
10
25
30
0069B
69
25
50
60
59
20
40
50
46
15
30
40
0105B
100
30
75
100
77
25
60
60
52
15
40
50
0115B
115
40
75
100
81
30
60
75
65
20
50
60
0135B 135 50 100 125 99 30 75 100 77 25 60 75
0184B
164
60
125
150
124
40
100
100
96
30
75
75
0200B
200
75
150
200
131
50
100
125
104
40
75
100
0229B
229
75
150
200
156
60
125
150
124
40
100
100
0250B
250
100
200
250
195
75
150
200
156
60
125
150
0352B
341
125
250
350
240
75
200
200
180
60
150
150
0397B
389
150
300
400
261
100
200
250
203
75
150
200
0410B
410
150
300
450
377
150
300
350
302
100
250
300
0550B
550
200
450
500
414
150
350
450
321
125
250
300
0580B 580 200 500 500 477 200 400 500 361 150 300 350