Programmable Parameters
9C – Analog A Maximum Adjustment
Range: 0% - 600% Default: 100%
Description: Calibrates the upper limit of the analog output to match the signal measured
on an external current measuring device.
9D – Analog A Minimum Adjustment
Range: 0% - 600% Default: 0%
Description: Calibrates the lower limit of the analog output to match the signal measured
on an external current measuring device.
9.12 10 Display
10A – Language
Options: English (default) Português
Chinese Français
Español Italiano
Deutsch Russian
Description: Selects which language the keypad will use to display messages and
feedback.
10B – Temperature Scale
Options: Celsius (default)
Fahrenheit
Description: Selects whether the soft starter will display temperatures in degrees Celsius
or Fahrenheit.
10C – Graph Timebase
Options: 30 seconds (default)
1 minute
30 minutes
1 hour
Description: Sets the graph time scale. The graph will progressively replace the old data
with new data.
10D – Graph Maximum Adjustment
Range: 0% – 600% Default: 400%
Description: Adjusts the upper limit of the performance graph.
10E – Graph Minimum Adjustment
Range: 0% – 600% Default: 0%
Description: Adjusts the lower limit of the performance graph.
10F – Current Calibration
Range: 85% - 115% Default: 100%
Description: Calibrates the soft starter's current monitoring circuits to match an external
current metering device.
Use the following formula to determine the necessary adjustment:
Calibration (%) =
Current shown on soft starter display
Current measured by external device
57