EasyManua.ls Logo

Nidec Digistart D4 - Display

Nidec Digistart D4
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programmable Parameters
9C Analog A Maximum Adjustment
Range: 0% - 600% Default: 100%
Description: Calibrates the upper limit of the analog output to match the signal measured
on an external current measuring device.
9D Analog A Minimum Adjustment
Range: 0% - 600% Default: 0%
Description: Calibrates the lower limit of the analog output to match the signal measured
on an external current measuring device.
9.12 10 Display
10A Language
Options: English (default) Português
Chinese Français
Español Italiano
Deutsch Russian
Description: Selects which language the keypad will use to display messages and
feedback.
10B Temperature Scale
Options: Celsius (default)
Fahrenheit
Description: Selects whether the soft starter will display temperatures in degrees Celsius
or Fahrenheit.
10C Graph Timebase
Options: 30 seconds (default)
1 minute
30 minutes
1 hour
Description: Sets the graph time scale. The graph will progressively replace the old data
with new data.
10D Graph Maximum Adjustment
Range: 0% 600% Default: 400%
Description: Adjusts the upper limit of the performance graph.
10E Graph Minimum Adjustment
Range: 0% 600% Default: 0%
Description: Adjusts the lower limit of the performance graph.
10F Current Calibration
Range: 85% - 115% Default: 100%
Description: Calibrates the soft starter's current monitoring circuits to match an external
current metering device.
Use the following formula to determine the necessary adjustment:
Calibration (%) =
Current shown on soft starter display
Current measured by external device
57

Table of Contents

Related product manuals