Installation
4.8 Quick Setup
The Quick Setup Menu makes it easy to configure the soft starter for common applications.
The soft starter guides you through the most common installation parameters, and
suggests a typical setting for the application. You can adjust each parameter to suit your
exact requirements.
All other parameters remain at default values. To change other parameter values or review
the default settings, use the menu (see Parameter List for details).
Always set parameter 1B Motor Full Load Current to match the motor's nameplate full load
current.
Application
Start Mode
Start Ramp
Time (seconds)
Initial Current
(%)
Current Limit
(%)
Adaptive Start
Profile
Stop Mode
Stop Time
(seconds)
Adaptive Stop
Profile
Pump Centrifugal
Adaptive
Control
10
200
500
Const.
accel.
Adaptive
Control
15
Const.
decel.
Pump bore
Adaptive
Control
3
200
500
Const.
accel.
Adaptive
Control
3
Const.
decel.
Pump Hydraulic
Constant
Current
2
200
350
n/a
Coast To
Stop
n/a
n/a
Fan Damped
Constant
Current
2
200
350
n/a
Coast To
Stop
n/a
n/a
Fan Undamped
Constant
Current
2
200
450
n/a
Coast To
Stop
n/a
n/a
Compressor Screw
Constant
Current
2
200
400
n/a
Coast To
Stop
n/a
n/a
Compressor Recip
Constant
Current
2
200
450
n/a
Coast To
Stop
n/a
n/a
Conveyor
Constant
Current
5
200
450
n/a
Coast To
Stop
n/a
n/a
Bow Thruster
Constant
Current
5
100
400
n/a
Coast To
Stop
n/a
n/a
Bandsaw
Constant
Current
2
200
450
n/a
Coast To
Stop
n/a
n/a
NOTE
The Adaptive Start and Stop Profile settings only apply when using Adaptive
Control. The settings are ignored for all other start and stop modes.