Programmable Parameters
10J User Parameter 3
Options: See parameter 10H User Parameter 1 for details.
Default: Motor pf
Description: Selects which information will be displayed on the programmable monitoring
screen. See parameter 10H User Parameter 1 for details.
10K User Parameter 4
Options: See parameter 10H User Parameter 1 for details.
Default: Motor Temperature (%)
Description: Selects which information will be displayed on the programmable monitoring
screen. See parameter 10H User Parameter 1 for details.
10L User Parameter 5
Options: See parameter 10H User Parameter 1 for details.
Default: Hours Run
Description: Selects which information will be displayed on the programmable monitoring
screen. See parameter 10H User Parameter 1 for details.
10M User Parameter 6
Options: See parameter 10H User Parameter 1 for details.
Default: Number of Starts
Description: Selects which information will be displayed on the programmable monitoring
screen. See parameter 10H User Parameter 1 for details.
9.13 12 Communications Card
12A Modbus Address
Range: 1 - 254 Default: 1
Description: Sets the Modbus RTU network address for the soft starter.
12B Modbus Baud Rate
Options: 4800
9600 (default)
19200
38400
Description: Selects the baud rate for Modbus RTU communications.
12C Modbus Parity
Options: None (default)
Odd
Even
10-bit
Description: Selects the parity for Modbus RTU communications.
12D Modbus Timeout
Options: Off (default)
10 seconds
60 seconds
100 seconds
Description: Selects the timeout for Modbus RTU communications.