6 Operating status messages
BU 0240 en-US-4920 87
Pos: 692 /A nleit ung en/El ek tr onik /FU und Star ter /6. M eldung en zum B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 004 [SK 180 E ... SK 5x xE/ SK 500P ] @ 2\mod_1347457006705_14638.docx @ 47225 @ @ 1
C004 4.1 Overcurrent measurem
"Overcurrent measurement"
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
• VFD is overloaded
• Drive sluggish, insufficiently sized,
• Ramps (P102/P103) too steep -> Increase ramp time
• Check motor data (P201 … P209)
• Switch off slip compensation (P212)
Pos: 693 /A nleit ung en/El ek tr onik /FU und Star ter /6. M eldung en zum B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 008 [SK 180 E ... SK 5x xE/ SK 500P ] @ 2\mod_1347457201563_14638.docx @ 47250 @ @ 1
C008 8.0 Parameter loss
Warning: One of the cyclically saved messages such as
operating hours or enabling time could not be saved
successfully.
The warning disappears as soon as saving can be
successfully performed.
Pos: 69 4 /Anlei tung en/El ektr onik/FU und Star ter/6 . Meld ungen zum B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 012 [SK 18 0E . .. SK 2x xE] @ 2\mod_1347457201968_14638.docx @ 47275 @ @ 1
C012 12.1 Limit moto./Customer
"Motor switch-off limit"
Warning: 80% of the drive switch-off limit (P534 [-01]) has
been exceeded.
• Reduce load on motor
• Set higher value in (P534 -[01])
12.2 Limit gen.
"Generator switch-off limit"
Warning: 80% of the generator switch-off limit (P534 [-02])
has been reached.
• Reduce load on motor
• Set higher value in (P534 [-02]).
12.3 Torque limit Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
12.4 Current limit Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
12.5 Load monitor Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
• Adjust load
• Change limit values ((P525) ... (P527))
• Increase delay time (P528)