6 Operating status messages
BU 0240 en-US-4920 87
Pos: 692 /A nleit ung en/El ek tr onik /FU und Star ter /6. M eldung en zum B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 004 [SK 180 E ... SK 5x xE/ SK 500P ] @ 2\mod_1347457006705_14638.docx @ 47225 @ @ 1
C004 4.1 Overcurrent measurem
"Overcurrent measurement"
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
VFD is overloaded
Drive sluggish, insufficiently sized,
Ramps (P102/P103) too steep -> Increase ramp time
Check motor data (P201 … P209)
Switch off slip compensation (P212)
Pos: 693 /A nleit ung en/El ek tr onik /FU und Star ter /6. M eldung en zum B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 008 [SK 180 E ... SK 5x xE/ SK 500P ] @ 2\mod_1347457201563_14638.docx @ 47250 @ @ 1
C008 8.0 Parameter loss
Warning: One of the cyclically saved messages such as
operating hours or enabling time could not be saved
successfully.
The warning disappears as soon as saving can be
successfully performed.
Pos: 69 4 /Anlei tung en/El ektr onik/FU und Star ter/6 . Meld ungen zum B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 012 [SK 18 0E . .. SK 2x xE] @ 2\mod_1347457201968_14638.docx @ 47275 @ @ 1
C012 12.1 Limit moto./Customer
"Motor switch-off limit"
Warning: 80% of the drive switch-off limit (P534 [-01]) has
been exceeded.
Reduce load on motor
Set higher value in (P534 -[01])
12.2 Limit gen.
"Generator switch-off limit"
Warning: 80% of the generator switch-off limit (P534 [-02])
has been reached.
Reduce load on motor
Set higher value in (P534 [-02]).
12.3 Torque limit Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
12.4 Current limit Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
12.5 Load monitor Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
Adjust load
Change limit values ((P525) ... (P527))
Increase delay time (P528)
Pos: 69 5 /Allg em ein/ Allg em eingül tig e M od ule/ ---------Seiten umbr uc h kom pakt --------- @ 13\mod_1476369695906_0.docx @ 2265496 @ @ 1

Table of Contents

Other manuals for Nord Drivesystems NORDAC FLEX SK 215E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nord Drivesystems NORDAC FLEX SK 215E Series and is the answer not in the manual?

Nord Drivesystems NORDAC FLEX SK 215E Series Specifications

General IconGeneral
BrandNord Drivesystems
ModelNORDAC FLEX SK 215E Series
CategoryInverter
LanguageEnglish

Related product manuals