5 Working with the unit control
Note: if you are working with the optional remote terminal read chapter
5.7 “Working with the remote terminal” rst. The operation of the remote
terminal deviates in some points from the operation at the humidier and
some adjustments are blocked via the remote terminal for safety reasons.
5.1 Factory settings
Ex works the unit control is set to the following standard settings:
Designation See chapter Parameter Factory setting
Dialogue language 5.4.2 Language country specic
Controller settings 5.4.3
Signal source SignalSource Analog
Control type Hum.Control Extern
Control signal Controlsign. 0-10V
Supply air limitation Lim. Control Off
Cylinder type 5.4.4 Cylinder unit specic
SC system 5.4.5
Status SC pump SC-Pump On
Operating time of the SC pump per hour On-Time unit specic
Capacity limitation 5.4.6
Set capacity limitation Power Limit 100 %
Time control capacity limitation Timer Off
Timer controlled operation of the humidier 5.4.7
Time control operation Timer Off
Water management 5.4.8
Water conductivity Conductivity >125 µS/cm
Drain factor Drain Factor 1.0
Operating behaviour in idle mode Idle Mode IdleOnly
Status forced draining function Force Drain On
Time delay forced draining Force Delay 72 hours
Date 5.4.9 Date to be set on site
Time of day 5.4.10 Time to be set on site
Display contrast 5.4.11 Contrast 50