27
If the timer is activated, up to eight switching points (events 1  8) with different humidity setpoints
can be dened. Each switching point is dened by a weekday or weekday range, the switching point
and the humidity setpoint.
Conguration notes:
the settings of an event remain active up to the next event.
the software does not check the plausibility of the timer settings. Therefore, make sure your
settings make sense.
the On/Off timer (see chapter 5.4.7) overrides the humidity setpoint timer.
5.4.3.6 Setting the proportional range for the internal P/PI controller
Note: This menu item is available only if the internal P or PI controller is activated.
Select “P-Band” in the control settings menu, then press the <Set> key.
In the upcoming modication dialogue set the proportional range in %rh for the internal P/PI controller.
Factory setting: 18 %rh
Setting range: 6...65 %rh
5.4.3.7 Setting the integral time for the internal PI controller
Note: This setting is available only if the internal PI controller is activated.
Select “Integr.-Time” in the control settings menu, then press the <Set> key.
In the upcoming modication dialogue set the integral time in minutes for the internal PI controller.
Factory setting: 8 minutes
Setting range: 1...60 minutes
5.4.3.8 Activating/Deactivating the supply air limitation
Note: This setting is available only if the control type is set to “External”, “Int. (P)” or “Int. (PI)”.
Select “Lim. Control” in the control settings menu, then press the <Set> key.
In the upcoming modication dialogue activate or deactivate the supply air limitation (Signal Z).
Factory setting: Off
Options: On, Off
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
Controls
Setpoint :Set
P-Band :18%rH
Integr.-Time:8min
Controlsign.:0-10V
Lim. Control:O
Esc Set
P-Band
18 %rH
18 %rH
Esc Set
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
Controls
Setpoint :Set
P-Band :18%rH
Integr.-Time:8min
Controlsign.:0-10V
Lim. Control:O
Esc Set
Integr.-Time
8 min
8 min
Esc Set
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
Controls
Integr.-Time:8min
Lim. Control:On
Limitsignal :0-10V
P-Band :18%rH
Limit Min :70%rH
Esc Set
Lim. Control
O
On
On
Esc Set