5.4.3.9 Selecting the supply air limitation signal
Note: This setting is available only if the external controller or the internal P or PI controller and the
supply air limitation are activated.
Select “Limitsignal” in the control settings menu, then press the <Set> key.
In the upcoming modication dialogue select the desired supply air limitation signal.
Factory setting: 0–10V
Options: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V, 0–20mA, 4–20mA
5.4.3.10 Settingthelowerlimitvalueforthesupplyairlimitation
Note: This setting is available only if the external controller or the internal P or PI controller and the
supply air limitation are activated.
Select “Limit Min” in the control settings menu, then press the <Set> key.
In the upcoming modication dialogue set the lower limit value in %rH for the supply air limitation.
Factory setting: 70 %rH
Options: 15 ... 95 %rH
5.4.3.11 Setting the upper limit value for the supply air limitation
Note: This setting is available only if the external controller or the internal P or PI controller and the
supply air limitation are activated.
Select “Limit Max” in the control settings menu, then press the <Set> key.
In the upcoming modication dialogue set the upper limit value in %rH for the supply air limitation.
Factory setting: 90 %rH
Setting range: 15 ... 95 %rH
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
Controls
Lim. Control:On
Limitsignal :0-10V
Limit Min :70%rH
Integr.-Time:8min
Limit Max :90%rH
Esc Set
Controls
Lim. Control:On
Limitsignal :0-10V
Limit Min :70%rH
Integr.-Time:8min
Limit Max :90%rH
Esc Set
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
4-20mA
0-20mA
3.2-16V
0-16V
Limitsignal
0-5VPoti
1-5V
0-10V
0-10V
2-10V
Esc Set
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
Controls
Lim. Control:On
Limitsignal :0-10V
Limit Min :70%rH
Integr.-Time:8min
Limit Max :90%rH
Esc Set
Limit.Min
70 %rH
70 %rH
Esc Set
Limit Max
90 %rH
90 %rH
Esc Set