5.4.8.3 Setting the operating mode for standby operation
Idle only operation
In this operating mode the cylinder is not emptied in standby operation.
Select “Idle Operat.” in the water management settings submenu, then press the <Set> key. In the
upcoming submenu select “Idle Mode”, then press the <Set> key.
In the upcoming modication dialogue set Idle Mode to “IdleOnly”, then press the <Set> key.
Standby operation with partial or complete draining of the steam cylinder
In this operating mode the cylinder is partly or fully drained after a certain time in standby opera
tion.
Select “Idle Operat.” in the water management settings submenu, then press the <Set> key. In the
upcoming Idle operation submenu set the parameters for standby operation with partial or complete
draining of the steam cylinder.
Settings:
Idle Mode”: Drain
Drain Mode”: Full” (complete draining of the cylinder) or “Partial(cylinder is drained so
far that the water does not touch the electrodes any longer)
Important: with outdoor operation it is mandatory to set the drain mode
to “Full”.
Settings
On/O Timer :Set
Water Manag.:Set
Date :11-08-31
Power Limit :Set
Time :12:00
Esc Set
Water Manag.
Drain Factor:1.0
Idle Operat.:Set
Force Drain :On
Conductivity:>125µS
Force Delay :72h
Esc Set
Idle Operat.
Drain Mode :Full
Drain Delay :72h
Idle Mode :Drain
Esc Set
Idle Operat.
Idle Mode :IdleOnly
Esc Set
Idle Mode
IdleOnly
Drain
KeepWarm
IdleOnly
A.Freeze
Esc Set
Settings
On/O Timer :Set
Water Manag.:Set
Date :11-08-31
Power Limit :Set
Time :12:00
Esc Set
Water Manag.
Drain Factor:1.0
Idle Operat.:Set
Force Drain :On
Conductivity:>125µS
Force Delay :72h
Esc Set
Idle Operat.
Idle Mode :IdleOnly
Esc Set
Idle Operat.
Drain Mode :Full
Drain Delay :72h
Idle Mode :Drain
Esc Set
Idle Operat.
Drain Mode :Full
Drain Delay :72h
Idle Mode :Drain
Esc Set
Idle Operat.
Drain Mode :Full
Drain Delay :72h
Idle Mode :Drain
Esc Set
Idle Mode
IdleOnly
Drain
KeepWarm
Drain
A.Freeze
Esc Set
Drain Mode
Partial
Full
Full
Esc Set
Drain Delay
72 h
72 h
Esc Set

Table of Contents