5.4.3.4 Conguringhumiditysetpoint
Note: This menu item is available only if the internal P or PI controller is activated.
With the parameters in the “Setpoint” submenu you determine whether the Nordmann RC4/DC4 is to
be controlled with a x humidity setpoint (factory setting) or whether it is to be operated timer controlled
with different humidity setpoints.
– Control with x humidity setpoint:
Select “Setpoint” in the control settings menu, then press the <Set> key.
Let the timer deactivated (Off) or deactivate the timer if necessary. Select “Setpoint”, then press the
<Set> key. In the upcoming modication dialogue set the desired humidity setpoint value (Factory
setting: 50 %rh, Setting range: 15...95 %rh).
Note: If the unit is congured to be controlled with a x humidity setpoint, the humidity setpoint can
be modied also directly in the main menu.
– Timer controlled with different humidity setpoints:
Select “Setpoint” in the control settings menu, then press the <Set> key.
Select “Timer”, then press the <Set> key. In the upcoming modication dialogue activate the timer
function and conrm the setting with the <Set> key.
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
Controls
Controlsign.:0-10V
Setpoint :Set
P-Band :18%rH
SignalSource:Analog
Integr.-Time:8min
Esc Set
Setpoint
Setpoint :50%rH
Timer :O
Esc Set
Setpoint
Setpoint :50%rH
Timer :O
Esc Set
Setpoint
50 %rH
50 %rH
Esc Set
Settings
Controls :Set
Cylinder :6564
SC-System :Set
Language :English
Power Limit :Set
Esc Set
Controls
Controlsign.:0-10V
Setpoint :Set
P-Band :18%rH
SignalSource:Analog
Integr.-Time:8min
Esc Set
Setpoint
Setpoint :50%rH
Timer :O
Esc Set
Setpoint
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc Set
Setpoint
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc Set
Event 2
Time :18:00
Setpoint :50%rH
Weekday :Mo-Fr
Esc Set
Event 2
Time :18:00
Setpoint :50%rH
Weekday :Mo-Fr
Esc Set
Event 2
Time :18:00
Setpoint :50%rH
Weekday :Mo-Fr
Esc Set
Timer
O
On
On
Esc Set
Weekday
O
Mo-Fr
Mo-Sa
Mo-Fr
Mo-Su
Esc Set
Setpoint
50 %rH
50 %rH
Esc Set
Time
18:00
18:00
Esc Set