Installation
3-2
Part 1105779-04
E 2014 Nordson Corporation
Make sure all console and flow module address and termination switch
settings are as described in Console Address and Termination Settings and
iFlow Module Address Settings in this section.
CAN AUX
CAN OUT
CAN IN
MASTER BACKPLANE
CAN AUX
CAN OUT
CAN IN
SLAVE BACKPLANE
Blue
White
Blue
White
Twisted-Pair
Shielded Cable
Master Console
Slave Console
Shield
Figure 3-1 CAN Network Cable Connections
Console CAN Network Address and Termination Settings
See Figure 3-2.
The CAN network terminator dipswitch and console address dipswitches on
the backplane must be set properly.
Network terminator dipswitch:
S Master console only: Set the network terminator to END (SW13
closed)
S Master and slave console: Set the master console to CONTINUOUS
(SW13 open) and the slave console to END (SW13 closed).
Network address dipswitch:
S Set the master console to 1 (SW11 closed, SW12 closed).
S Set the slave console to 2 (SW11 closed, SW12 open).