Installation
3-3
Part 1105779-04
E 2014 Nordson Corporation
12
3
SW1
Open
CAN
AUX
CAN
OUT
CAN
IN
Network
Terminator
Console
Address
SW1-1 SW1-2 Console
Closed Closed 1
Closed Open 2
Console Address
Switch Settings
Closed = End
Open = Continuous
Rocker switch
(side views)
Closed
(top in)
Open
(bottom in)
Slide switch
(side views)
Closed
(on)
Open
Figure 3-2 CAN Network Connections, Console Addresses, and Termination
iFlow Module Dipswitch Settings
The dipswitches on the iFlow digital flow modules set:
S gun air flow triggering
S console address
S module address
Each iFlow module must have a unique network address. The system will
not be able to operate flow modules with duplicate addresses, and will notify
the operator if it detects two modules with the same address.
The module address consists of the console number (1 or 2) and the
number of the module (1−8) within the console.
See Figure 3-3 and Table 3-1.
Air Flow (SW4−1, 2)
Sure Coat guns− Set switches 1 and 2 to Continuous (down).
Versa-Spray guns with gun air option− Set switches 1 and 2 to Trigger (up).
Console Address (SW4−3, 4): Set switches 3 and 4 to the console
address, which is the same as the address set at the backplane dipswitch
shown in Figure 3-2.
Module Number (SW3): Set the rotary dipswitch on each module to the
correct module number. The modules are numbered as shown in the
module arrangement chart in Figure 3-3.