3-40
Installation guidelines
AN2016 Cabinet User Guide Rel 1.0 Standard May 1999
Procedure 3-12 (continued)
Installing batteries
Step Action
2
Remove the battery cover according to battery manufacturer 's instructions.
3
Slide the first string of batteries lengthwise with terminals facing front, into the
battery compartment.
4
Push the batteries all the way into the back of the battery compartment until
the battery touches the divider wall.
5
Leave a gap between each battery from 1/4-in. to 3/8- in.
6
Install the intercell connectors (supplied by the battery manufacturer)
according to Figure 3-26.
a.
Install one intercell connector from the POSITIVE (+) terminal of Battery
#1 to the NEGATIVE (-) terminal of Battery #2.
b.
Install one intercell connector from the POSITIVE (+) terminal of Battery
#2 to the NEGATIVE (-) terminal of Battery #3.
c.
Install one intercell connector from the POSITIVE (+) terminal of Battery
#3 to the NEGATIVE (-) terminal of Battery #4.
7
Install the Anderson connectors shipped in the battery cable kit as follows:
a.
Connect the BLACK POSITIVE (+) lead to the POSITIVE (+) terminal of
Battery #4.
b.
Connect the RED NEGATIVE (-) lead to the NEGATIVE terminal of
Battery #1.
8
Plug in the Anderson connector into the mating Anderson connector directly
above the string.
Note:
Verify the polarity of the connectors and battery terminals match.
9
Install the next string of batteries into the battery compartment. Repeat steps
3 through
8.
—end—