Introduction
1-2 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
6WDQGDUG)HDWXUHVDQG2SWLRQV
Control panel features and options that affect installation include:
• Four Notification Appliance Circuit (NAC) bell circuits standard, expandable to 68
total (Class A or B).
• EIA-485 connections for wiring ACS annunciators (including LDM custom
graphic annunciators).
• Optional modules include: 4XTM transmitter, UDACT Universal Digital Alarm
Communicator/Transmitter, ACM-8R remote relay module to increase point
capacity, and audio and voice components.
• Autoprogram feature for faster programming of new devices.
• Optional LCD-80 allows monitoring the system—up to 6,000 feet from the control
panel.
The control panel provides 6.0 amps of usable output power (standard).
6\VWHP/LPLWDWLRQV
System expansion must comply with:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply, including auxiliary power
supplies used for notification appliances.
3. The capacity of the Secondary Power Source (standby batteries).
Refer to System Components, for descriptions of the various optional modules. Refer
to Section 2,
Installation
for installation information.