EasyManua.ls Logo

Notifier AFP-400 - Installing a 4 XTM Module (Remote Station Fire Alarm)

Notifier AFP-400
207 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
,QVWDOODWLRQ
Installing a 4XTM Module (Remote Station Fire Alarm)
2-22 AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
,QVWDOOLQJD;700RGXOH5H PRWH 6WDWLRQ)LUH$ODUP
0RXQWLQ
J
WKH0RGXOH
Install the 4XTM module by following these steps:
Table 2-9 Mounting a 4XTM Module
Figure 2-25 shows where to mount a 4XTM module on the MPS-400 board:
)LJXUH  0RXQWLQJ D ;70 0RGXOH
;70(OHFWULFDO5H
T
XLUHPHQWV
Electrical requirements for local energy municipal Box service (NFPA 72-1993
Auxiliary Protective Fire Alarm System) are:
1RWH 7KH /RFDO (QHUJ\
0XQLFLSDO %R[ &LUFXLW LV
QRQSRZHUOLPLWHG 0DLQWDLQ DW
OHDVW D  LQFK VSDFLQJ
EHWZHHQ WKH 0XQLFLSDO %R[
&LUFXLW ZLULQJ DQG DOO
SRZHUOLPLWHG FLUFXLW ZLULQJ
Electrical requirements for remote station service (NFPA 72-1993 Remote Station Protective Fire
Alarm System) are:
Step Action
1 Install the standoffs (provided) into the holes next to TB1 on the MPS-400 board.
2 Carefully align the pins on the MPS-400 PC board with the connector on the 4XTM
board.
3 Press firmly on the 4XTM board until the board locks in place on the standoffs.
4 Screw the 4XTM board to the standoffs.
Supervisory current 5.0 mA
Trip current 0.35 A (subtracted from NAC power)
Coil voltage 3.65 VDC
Coil resistance 14.6 ohms
;70
036
7%
6WDQGRII
Wire resistance (panel and trip coil) Maximum of 3.0 ohms
Maximum load for each circuit 10 mA
Reverse polarity output voltage 24 VDC (nominal) 28 VDC (max)
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP-400

Related product manuals