Installing a 4XTM Module (Remote Station Fire Alarm)
,QVWDOODWLRQ
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-23
&RQQHFWLQJWKH;700RGXOH
Push the Disconnect Switch (Figure 2-26) down to prevent unwanted activation of the
Municipal Box during testing of the control panel.
The 4XTM Disconnect LED lights while the Municipal Box is disconnected; and
The CPU System Trouble LED lights to indicate disconnected and/or open circuit
conditions on the Municipal Box.
During trouble conditions, you can transmit a trouble indication through an open circuit
signal on the Alarm Reverse-Polarity output. Do this by cutting the TBL jumper
(Figure 2-26). Figure 2-26 shows connections to the 4XTM with polarities shown in
the activated position:
)LJXUH  ;70 7UDQVPLWWHU 0RGXOH 3RODULWLHV VKRZQ LQ DFWLYDWHG SRVLWLRQV
0XQLFLSDO %R[
QRQSRZHUOLPLWHG
'LVFRQQHFW 6ZLWFK
7%/ -XPSHU
:LULQJ IURP WKHVH WHUPLQDOV FDQ
H[LW WKH SURWHFWHG SUHPLVHV
5HPRWH $ODUP SRZHUOLPLWHG
5HPRWH 7URXEOH SRZHUOLPLWHG
²
²
1R FRQQHFWLRQ
'LVFRQQHFW /('
²