AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 3-1
7HVWLQJWKH6\VWHP
$FFHSWDQFH7HVW
When finished with the original installation and all modifications, conduct a complete
operational test on the entire installation to verify compliance with applicable NFPA
standards. Testing should be conducted by a factory-trained fire alarm technician in the
presence of a representative of the Authority Having Jurisdiction and the owner's
representative. Follow procedures outlined in NFPA Standard 72-1993, Chapter 7,
Inspection, Testing and Maintenance.
3 HULRGLF7HVWLQJDQG6HUYLFH
Periodic testing and servicing of the control panel, all initiating and notification
devices, and any other associated equipment is essential to ensure proper and reliable
operation. Test and service the control panel according to the schedules and procedures
outlined in the following documents:
NFPA Standard 72-1993, Chapter 7, Inspection, Testing and Maintenance.
Service manuals and instructions for the peripheral devices installed in your
system. Correct any trouble condition or malfunction immediately.
2SHUDWLRQDO&KHFNV
Between formal periodic testing and servicing intervals, the following operation checks
should be performed monthly, or more frequently when required by the Authority
Having Jurisdiction.
1RWH
7KH EDWWHU\ WHVW UHTXLUHV
IXOO\ FKDUJHG EDWWHULHV ,I
EDWWHULHV DUH QHZ RU GLVFKDUJHG
GXH WR D UHFHQW SRZHU RXWDJH
DOORZ WKH EDWWHULHV WR FKDUJH IRU
 KRXUV EHIRUH WHVWLQJ
Check that the green AC POWER LED lights.
Check that all yellow LEDs are off.
Press and hold the LAMP TEST switch. Verify that all LEDs and all LCD display segments
work.
Before proceeding: a) notify the fire department and the central alarm receiving station if
transmitting alarm conditions; b) notify facility personnel of the test so that alarm sounding
devices are disregarded during the test period; and c) when necessary, disable activation of
alarm notification appliances and speakers to prevent their sounding.
Activate an Initiating Device Circuit using an alarm initiating device and check that all
active notification appliances function. Reset the alarm initiating device, the control panel,
and any other associated equipment. In voice alarm applications, confirm that the proper
tone(s) and/or messages sound during alarm conditions. Select the paging function and
confirm that the message can be heard in the affected fire zones. Repeat the above step with
each Initiating Device Circuit.
On systems equipped with a fire fighters telephone circuit, make a call from a telephone
circuit and confirm a ring tone. Answer the call and confirm communication with the
incoming caller. End the call and repeat for each telephone circuit in the system.
Remove AC power, activate an Initiating Device Circuit through an alarm initiating device,
and check that active notification appliances sound, and alarm indicators illuminate.
Measure the battery voltage with notification appliances active. Replace any battery with a
terminal voltage less than 21.6 VDC and reapply AC Power.
Return all circuits to their pre-test condition.
Check that all yellow LEDs are off and the green AC POWER LED is on.
Notify fire, central station and/or building personnel when you finish testing the system.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-400 and is the answer not in the manual?

Notifier AFP-400 Specifications

General IconGeneral
BrandNotifier
ModelAFP-400
CategoryControl Panel
LanguageEnglish

Related product manuals