Programming 15088:J 10/22/99
3-71
Example # 5: CCBE for NOTIFIRENET
Node 1 will activate L1M1 if Z1 is active locally. Node 1 will activate L1M2 if Z200 is active locally or in both
Nodes 7 and 43 simultaneously. Node 43 will activate L1M2 if Z200 is not active locally and not activated in
Node 7.
L1D1
Z1
L1M1
CMX
L1D2
RZON
Z200
L1M2
CMX
(Z1)
(Z200)
OR(Z1)
OR(Z200)
( )
OR( )
AND(N7Z200 N43Z200)
NODE 1
(Z1)
(Z200)
OR(Z1)
OR(Z200)
( )
OR( )
OR( )
L1D1
Z1
L1M1
CMX
L1D2
RZON
Z200
L1M2
CMX
NODE 7
NODE 43
(Z1)
OR(Z1)
NOT(Z200)
( )
OR( )
OR(N7Z200)
L1D1
Z1
L1M1
CMX
RZON
Z200
L1M2
CMX