Installation 15088:J 10/22/99
Figure 4.10-4 Two Independent Style 4 SLC Loops
LIB-400
CMX
ISO-X
ISO-X
MMX
XPP
BGX-101L
MMX-101
BX-501 Base
SLC Loop Maximums:
99 Module Addresses
99 Detector Addresses
40 ohms total loop resistance (LIB-200)
50 ohms total loop resistance (LIB-200A/LIB-400)
10,000 feet (3048 meters) of loop (LIB-200)
12,500 feet (3810 meters) of loop (LIB-200A/LIB-400)