4-22
Security 15088:J 10/22/99
NIB-96
NIB-96 Network Interface Board
Protected Premises Unit (Slave)
Annunciator Point: AssP1
Type ID: AAST
Central Station (Master)
Monitor Module Point
Address: LXXMYY
Type ID: MON
Control-By-Event: (Installer Specified)
Custom Label: Installer Specified.
Tracking: Yes - Default fire alarm
conditions will restore auto-
matically at the Central Sta-
tion after reset at the Pro-
tected Premises.
No - Default fire alarm condi-
tions will latch in the Central
Station until reset at the
Central Station and at the
Protected Premises if the
NIB has been configured to
prevent reset from the Cen-
tral Station - short condition
only.
Annunciator: Optional.
The first point of the NIB-96 interface reports
any trouble condition in the Protected Premises
to the Central Station. If the installer fails to pro-
gram the Protected Premises Unit properly,
leaving fire alarm initiation devices without a cor-
responding NIB point, an alarm from such an ini-
tiating device will cause the first NIB point to in-
dicate a default fire alarm condition at the Cen-
tral Station.
Assign no device to this corresponding point.
Control Module Point
Address: LXXMYY
Type ID: CON
Control-By-Event: ( )
Custom Label: Installer Specified.
Signal Silence: Yes
Walk Test: No
Annunciator: No
Assign no device to this corresponding point.
Point
1
2
3
4
Annunciator Point: AssP2
Type ID: AMON
Annunciator Point: AssP3
Type ID:
ARES - Select the ARES Type ID if reset of the
Protected Premises Unit is to be
permitted at the Central Station.
AMON - Select the AMON Type ID if reset of
the Protected Premises Unit is not to
be permitted at the Central Station.
Annunciator Point: AssP4
Type ID: AMON
Figure 1.3-10 Programming Key (continued):
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AM2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AM2020 and is the answer not in the manual?

Notifier AM2020 Specifications

General IconGeneral
BrandNotifier
ModelAM2020
CategoryFire Alarms
LanguageEnglish

Related product manuals