LCD-160 P/N 51850:A 09/26/2003 39
Operating Screens Screen Displays
More Information
Pressing the soft key to the left of MORE INFORMATION on the “Event Counts Display” brings up
the “More Information” screen. This screen contains additional information about the event shown
in the Event Reporting Format
Figure 24 More Information Screen
Lines 1- 4 - Event information displayed in the Event Reporting Format. See “Event Reporting
Format” on page 26.
Lines 6 through 9 - The Custom Action Message programmed for the point in alarm
Line 11 and 14 - These lines exist only for smoke/heat detectors. They do not display for wireless
smoke detectors.
Line 11
VALUES:
121% OF ALARM - This field gives the detector reading as it relates to its preprogrammed alarm
level value (indicated in the next line on the screen). The example above shows the detector
exceeding the alarm level by 21%.
145% OF PREALARM - This field gives the detector reading as it relates to its preprogrammed
prealarm level value (indicated in the next line on the screen). The example above shows the
detector exceeding the prealarm level by 45%.
Line 12
ALARM: 6=1.66% - Six is the preprogrammed alarm level value for this detector: its value is
1.66%, indicating the percent per foot obscuration value assigned to level 6.
PREALARM: 3=0.47% - Three is the preprogrammed pre-alarm level value for this detector: its
value is 0.47%, indicating the percent per foot obscuration value assigned to level 3.
Line 13
ACTION/STATUS: NONE/VERY CLEAN - This displays the maintenance status of the device. The
message that appears in this field depends on the drift compensation value. A detector will
automatically compensate for environmental contaminants and other factors over time, until
the tolerance value has been exceeded. The FACP will signal a trouble condition when this
level has been reached. Refer to the following table for messages and required action.
ACKNOWLEDGED FIRE ALARM
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z005 SMOKE(PHOTO)
11:58:45A WED JUN 26, 2003 N112L03D052
MORE INFORMATION
CALL 203-555-1212
GO TO ALARM SITE AND INVESTIGATE
APPROACH THE ALARM LOCATION WITH CAUTION
BRING CELL PHONE AND REPORT WHEN ON SITE
VALUES: 121% OF ALARM, 145% OF PREALARM
ALARM: 6= 1.66%, PREALARM: 3= 0.47%
ACTION/STATUS: NONE/VERY CLEAN
PEAKS:56% VERIFY COUNT:02 CO-OP:D100,158
12:22:34P WED JUN 26, 2003
BACK