part
3
O
PERATION
: C
ONFIGURATION
M
ODE
90
Remote Setpoint Option cont.
Display Action Response
REMOTE SETPOINT 3 SUBMENU:
Press ENTER 9) Display flashes 1st digit of previous selection for 
"Remote Setpoint 3" value.
Press MAX & MIN 10) Enter a new 
"Remote Setpoint 3" value.
Press ENTER 11) Display flashes 
"
strd
" message and the display shows "Reset" ending the
Configuration Mode.
RESET:
The controller automatically resets after the last menu of the Configuration Mode
has been entered.  After the controller resets, the controller advances to the 
Run Mode.
In order to select r.SP remotely connect Bi1 and Bi2 as follows:
Bi1 Bi2
r.SP.1 GND GND
r.SP.2 OPEN GND
r.SP.3 GND OPEN
Setpoint 1 OPEN OPEN
RST
R.SP.3
275.0