EasyManua.ls Logo

Omega PLATINUM Series - Connecting Power

Omega PLATINUM Series
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PLATINUM
TM
Series Controllers User’s Guide
M5451 Omega Engineering | www.omega.com
11
Wiring Instructions
Caution: Do not connect power to your device until you have completed all input
and output connections. Failure to do so may result in injury!
Use Copper Conductors
rated for 75
C min
only for Power Connections
Figure 3 CN16Pt and CN32Pt Models: Back Panel Connections
3.2 Connecting Power
Connect the main power connections to pins 7 and 8 of the 8-pin power / output connector as shown in
Figure 4.
Figure 4 Main Power Connections
For the low-voltage power option, maintain the same degree of
protection as the standard high-
voltage input power units (90240 Vac) by
using a Safety Agency Approved DC or AC source with
the same Overvoltage Category and pollution degree as the standard AC unit (90300 Vac).
The Safety European Standard EN61010-1 for measurement, control, and laboratory equipment
requires that fuses must be specified based on IEC127. This standard specifies the letter code “T”
for a Time-lag fuse.
Ethernet Communications Status
LEDs if EIP Option Installed
Ethernet Connector if EIP
Option Installed
8-Pin Power / Outputs Connector
10-Pin Input Connector
USB Connector (on side,
cable stub shown)
110 ~ 300 Vdc
110 ~ 300 Vdc

Table of Contents