OMICRON 25
Application
3 Application
3.1 Preparations on site
DANGER
Death or severe injury caused by high voltage or current
Prior to connecting a test object to the CP TD1, the following steps need to be carried out
by an authorized employee of the utility:
Turn off and disconnect the high voltage from the test object.
Protect yourself and your working environment against an accidental re-connection of
high voltage by other persons and circumstances.
Verify a safe isolation of the test object.
Earth-connect and shorten out the test object’s terminals using a grounding set.
Protect yourself and your working environment with a suitable protection against other
(possibly live) circuits.
Protect others from accessing the dangerous area and accidentally touching live parts
by setting up a suitable barrier and, if applicable, warning lights.
If there is a longer distance between the location of the CP TD1 and the area of danger
(that is, the test object), a second person with an additional "Emergency Stop" button
is required.

Table of Contents

Other manuals for Omicron CP TD1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omicron CP TD1 and is the answer not in the manual?

Omicron CP TD1 Specifications

General IconGeneral
BrandOmicron
ModelCP TD1
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals