CP TD1 User Manual
30 OMICRON
3. If you are using the CPC 100 or CPC 80: Turn the safety key to "lock" (vertical) and remove the key
to avoid anybody accidentally turning on the high voltage.
4. Earth-connect and shorten out the test object’s terminals using a grounding set.
5. Plug off the high-voltage cable from the high-voltage output of the CP TD1.
6. Disconnect the cables from the CP TD1.