Functions
Rotation Direction Monitor [d003]
Displays the rotation direction of the Inverter.
The RUN LED indicator is lit during forward/reverse rotation.
In general, the forward direction of the motor is the counterclockwise direction as viewed from
the axial direction.
PID Feedback Value Monitor [d004]
When "01: Enabled" or "02: Reverse output enabled" is selected in PID Selection (A071), the
PID feedback value can be monitored.
Also, conversion is possible using PID Scale (A075).
"d004 display" = "Feedback value [%]" × PID Scale (A075)
Parameter
No.
Function name Data
Default
setting
Unit
d003
Rotation Direction
Monitor
F: Forward
−−o: Stop
r: Reverse
Forward
Parameter
No.
Function name Data
Default
setting
Unit
d004
PID Feedback
Value Monitor
0.00 to 99.99 (Displayed in increments of
0.01.)
−−
100.0 to 999.9 (Displayed in increments
of 0.1.)
1,000. to 9,999. (Displayed in increments
of 1.)
1,000 to 9,999 (Displayed in increments
of 10.)
100 to 999 (Displayed in increments of
1,000.)
A075 PID Scale
0.01 to 99.99 (Displayed in increments of
0.01.)
1.00 Time
Related functions A071, A075