EasyManua.ls Logo

Omron 3G3MX2 - Multiple Holding Register Read or Write [17 H]

Omron 3G3MX2
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-17
6-5 Explanation of Each Parameter No.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6
Communication Function
Multiple Holding Register Read or Write [17h]
Writes into or reads from consecutive multiple registers.
Example) Write 50,00 Hz into Output Frequency Setting (F001) of the Inverter with
Slave Address "1," and Read Output Frequency Monitor Value (d001).
(Register address) = (Register number)
1
(Register address) = (Register number)
1
0000 1388h
5000d
50.00 Hz
0000 1388h 5000d 50.00 Hz
Query:
Response:
*1. Note that the holding register start address is smaller by 1 than the register number. The register
number less 1 corresponds to the register address.
Refer to "Exceptional Response" on page 6-18 if writing into or reading from multiple registers
cannot be performed normally.
No. Field name
Example
(Hex)
1 Slave address 01
2 Parameter No. 17
3
Read register start address (MSB)
*1
10
4
Read register start address (LSB)
*1
00
5 Number of read registers (MSB) 00
6 Number of read registers (LSB) 02
7
Write register start address (MSB)
*1
00
8
Write register start address (LSB)
*1
00
9 Number of write registers (MSB) 00
10 Number of write registers (LSB) 02
11 Number of written data bytes n 04
12 Written data 1 (MSB) 00
13 Written data 1 (LSB) 00
14 Written data 2 (MSB) 13
15 Written data 2 (LSB) 88
16 CRC-16 (MSB) F4
17 CRC-16 (LSB) 86
No. Field name
Example
(Hex)
1 Slave address 01
2 Parameter No. 17
3 Number of read data bytes n 04
4 Read data 1 (MSB) 00
5 Read data 1 (LSB) 00
6 Read data 2 (MSB) 13
7 Read data 2 (LSB) 88
8 CRC-16 (MSB) F4
9 CRC-16 (LSB) 71

Table of Contents