5-6
5-1 Monitor Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
5
Functions
Torque Bias Monitor [d010]
During sensorless vector control, the currently set torque bias amount is displayed.
Output Torque Monitor [d012]
Displays an estimated value of the Inverter's output torque.
Note: The power running direction is positive and regeneration direction is negative during forward
rotation, while the power running direction is negative and regeneration direction is positive during
reverse rotation.
This display is shown only when the sensorless vector control is selected. If any other control
mode is selected, the correct value is not displayed.
Output Voltage Monitor [d013]
Displays the output voltage of the Inverter.
Set Motor Incoming Voltage Selection (A082/A282) correctly. The correct value may not be
displayed.
Parameter
No.
Function name Data
Default
setting
Unit
d010 Torque Bias Monitor 200. to 200. %
Related functions A044, P036, P037, P038
Parameter
No.
Function name Data
Default
setting
Unit
d012
Output Torque
Monitor
200. to 200.
%
Related functions A044/A244
Parameter
No.
Function name Data
Default
setting
Unit
d013
Output Voltage
Monitor
0.0 to 600.0
V