5-34
5-3 Input/Output Terminals
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
5
Functions
Multi-function Output Terminal Contact Selection
Whether to apply the NO or NC contact output specification can be set individually for each of
multi-function output terminals P1/EDM, P2 and multi-function relay output terminal MA, MB.
Multi-function output terminals P1/EDM, P2 are open-collector output, while multi-function
relay output terminal MA, MB are relay output.
Specifications of Multi-function Output Terminals P1/EDM to P2
Below are the specifications of multi-function output terminals P1/EDM and P2.
Parameter
No.
Function name Data
Default
setting
Unit
C031
C032
Multi-function Output
Terminal P1/EDM
Contact Selection
Multi-function Output
Terminal P2 Contact
Selection
00: NO (NO contact) at P1, P2, MA,
NC (NC contact) at MB
00
01: NC (NC contact) at P1, P2, MA,
NO (NO contact) at MB
C036
Multi-function Relay
Output (MA, MB)
Contact Selection
00: NO (NO contact) at P1, P2, MA,
NC (NC contact) at MB
01
01: NC (NC contact) at P1, P2, MA,
NO (NO contact) at MB
C031 to C032 set
values
Power
supply
Inverter status Output signal status
00
(NO contact)
ON
Normal OFF (No conduction)
Operating (Error) ON (Conduction)
OFF Indeterminable
01
(NC contact)
ON
Normal ON (Conduction)
Operating (Error) OFF (No conduction)
OFF Indeterminable
Electrical characteristics
Between each terminal and PC
Voltage drop 4 V max. at power-on
Max. allowable voltage: 27 VDC
Allowable max. current: 50 mA
PC P2 P1
Inverter interior