5-35
5-3 Input/Output Terminals
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
5
Functions
Specification of Multi-function Relay Output Terminals
Multi-function relay output terminals has a SPDT contact specification. Below is the operation.
Example of use as an alarm
C036
Set value
Power
supply
Inverter
status
Output terminal status
MA-MC MB-MC
00
ON
Abnormal
Closed Open
Normal
Open Closed
OFF
Open Closed
01
(Default
value)
ON
Abnormal
Open Closed
Normal
Closed Open
OFF
Open Closed
Resistance load Inductive load
MA-MC
Max. contact
capacity
250 VAC, 2 A
30 VDC, 3 A
250 VAC, 0.2 A
30 VDC, 0.6 A
Min. contact
capacity
100 VAC, 10 mA
5 VDC, 100 mA
MB-MC
Max. contact
capacity
250 VAC, 1 A
30 VDC, 1 A
250 VAC, 0.2 A
30 VDC, 0.2 A
Min. contact
capacity
100 VAC, 10 mA
5 VDC, 100 mA
MC
Inverter interior
MA MB