EasyManua.ls Logo

Omron 3G3MX2 - Writing into Multiple Coils [0 Fh]

Omron 3G3MX2
440 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-14
6-5 Explanation of Each Parameter No.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6
Communication Function
Writing Into Multiple Coils [0Fh]
Rewrites consecutive multiple coils.
Example) Change the statuses of multi-function input terminals S1 to S7/EB of the
Inverter with the slave address "1".
Change multi-function input terminals S1 to S7/EB to the statuses shown in the table below.
(Coil address) = (Coil number) 1
17h = 0001 0111
Query:
Function name Data
Coil No. 0007h 0008h 0009h 000Ah 000Bh 000Ch 000Dh
Multi-function input terminals S1 S2 S3/GS1 S4/GS2 S5/TH S6 S7/EB
Terminal status ON ON ON OFF ON OFF OFF
Input terminal S7/EB
Input terminal S1
No. Field name
Example
(Hex)
1 Slave address
*1
01
2 Parameter No. 0F
3 Coil start address (MSB)
*2
00
4 Coil start address (LSB)
*2
06
5 Number of coils (MSB) 00
6 Number of coils (LSB) 07
7 Number of bytes 02
8 Change data (MSB) 17
9 Change data (LSB) 00
10 CRC-16 (MSB) 06
CRC-16 (LSB) 98