4-1
4-1 Monitor Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
   4
Parameter List
4-1 Monitor Mode
The description in "d001" is always displayed in the default setting at power-on. To fix the
optional display, change the setting in "b038".
The displayed parameters are limited in the default setting. To display all parameters, set Display
Selection (b037) to "00 (Complete display)".
Setting Soft Lock Selection (b031) to "10" permits data change during RUN.
Data ranges given in parentheses are for high-frequency mode. Refer to page 5-178 for details. 
Parameter 
No. 
Function name Monitor or data range
Default 
setting
Data can 
be set 
during 
RUN
Data can 
be 
changed 
during 
RUN
Unit
Page
d001
Output 
Frequency 
Monitor
0.00 to 99.99
− yes yes Hz 5-1
100.0 to 1,000. (High-frequency 
mode)
d002
Output Current 
Monitor
0.0 to 655.3 −− −A5-1
d003
Rotation 
Direction 
Monitor
F: Forward
o: Stop
r: Reverse
−− −−5-2
d004
PID Feedback 
Value Monitor
0.00 to 99.99
100.0 to 999.9
1000. to 9999.
1000 to 9999(10000 to 99990)
100 to 999(100000 to 999000)
−− −−5-2
d005
Multi-function 
Input Monitor
−− −−5-3
d006
Multi-function 
Output Monitor
−− −−5-3
d007
Output 
Frequency 
Monitor (after 
conversion)
0.00 to 99.99
100.0 to 999.9
1000. to 4000 (9999)
1000 to 4000 (9999/100)
− yes yes − 5-4
d008
Real Frequency 
Monitor
(−100/−999.) −400. to −100.
−99.9 to −10.0
−9.99 to −0.00
0.00 to 99.99
100.0 to 400.0 (400.1 to 999.9/1000.)
−− −Hz 5-5
d009
Torque 
Reference 
Monitor
−200. to +200. −− −%5-5
d010
Torque Bias 
Monitor
−200. to +200. −− −%5-6
d012
Output Torque 
Monitor
−200. to +200. −− −%5-6
d013
Output Voltage 
Monitor
0.0 to 600.0 −− −V5-6
ON
OFF
S7 S6 S5 S4 S3 S2 S1
(Example) 
Terminal S1, S2: ON
Terminal S3 to S7: OFF
ON
OFF
MA P2 P1
(Example) 
Terminal P1, P2: ON
Terminal AL: OFF