4-2
4-1 Monitor Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
   4
Parameter List
d014
Input Power 
Monitor
0.0 to 100.0 −− −kW 5-7
d015
Integrated 
Power Monitor
0.0 to 999.9
1000. to 9999.
1000 to 9999 (10000 to 99990)
100 to 999 (100000 to 999000)
−− −−5-7
d016
Total RUN 
Time
0.0 to 9999.
1000 to 9999 (10000 to 99990)
100 to 999 (100000 to 999000)
−− −h5-8
d017 Power ON Time 
0.0 to 9999.
1000 to 9999 (10000 to 99990)
100 to 999 (100000 to 999000)
−− −h5-8
d018
Fin 
Temperature 
Monitor
−20.0 to 150.0 −− −°C5-8
d022
Life 
Assessment 
Monitor
−− −−5-9
d023
(Reserved) −−−−−−
d024
d025
d026
d027
d029
Position 
Command 
Monitor
−268435455 to 268435455
(Displays MSB 4 digits including "−")
−− −−5-9
d030
Current 
Position 
Monitor
−268435455 to 268435455
(Displays MSB 4 digits including "−")
−− −−5-9
d050
User Selection 
Monitor (2 
types)
Monitor data selected by b160/b161 is 
displayed.
−− −−5-10
d060
Inverter Mode 
Monitor
The currently set mode is displayed. 
I-C (IM motor heavy load)
I-V (IM motor light load)
H-I (IM motor high frequency)
−− −−5-10
d080 Fault Counter
0. to 9999.
1000 to 6553 (10000 to 65530)
−− −Time 5-11
d081
Fault Monitor 1 
(Latest)
Cause
→Frequency (Hz)
→Current (A)
→Voltage between PNs (V)
→RUN time (h)
→Power ON time (h)
−− −−5-11
d082 Fault Monitor 2
d083 Fault Monitor 3
d084 Fault Monitor 4
d085 Fault Monitor 5
d086 Fault Monitor 6
Parameter 
No. 
Function name Monitor or data range
Default 
setting
Data can 
be set 
during 
RUN
Data can 
be 
changed 
during 
RUN
Unit
Page
21
1: Capacitor on main 
circuit board 
2: Cooling fan