EasyManua.ls Logo

Omron 3G3MX2 - Constant Torque Characteristics; Reduced Torque Characteristics

Omron 3G3MX2
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-111
5-9 Functions Relating to Protections, Warnings and Various Output Signals
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
5
Functions
Reduced Torque Characteristics
Multiplied by the time limit characteristics set in b012/212 for each frequency.
Example) 3G3MX2-**, base frequency 60 Hz, light load setting (rating 9.6 A = b012)
Constant Torque Characteristics
Do not skip this setting when using a constant torque motor.
Example) 3G3MX2-**, base frequency 60 Hz, heavy load setting (rating 8.0 A = b012)
Reduction
multiple
Base frequency
Inverter output frequency (Hz)
×
1.0
×
0.8
×
0.6
0
0
5
6
16
20
50
60
60 Hz (reduction multiple:
×
1.0) 20 Hz (reduction multiple:
×
0.8)
A
larm
time (s)
Motor
current (A)
Alarm
time (s)
Motor
current (A)
60
0.5
0
11.1 11.5 14.4
[A]
(116%)(120%)
(150%)
60
3.0
0
8.9 9.2 11.5
[A]
(92.8%)(96%)
(120%)
Reduction
multiple
Inverter output
frequency (Hz)
×
1.0
×
0.8
0
3
60
60 Hz (reduction multiple:
×
1.0)
Less than 3 Hz (reduction multiple:
×
0.8)
A
larm
time (s)
Motor current (A)
Alarm
time (s)
60
3.0
0
8.72 12 16
[A]
(109%)(150%)
(200%)
60
3.0
0
7.0 9.6 12.8
[A]
(87.2%)(120%)
(160%)
Motor current (A)

Table of Contents