5-74
5-6 Operation Functions
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
5
Functions
Reference
When the PID function is used, do not set the Analog Input Filter to 500 ms (A016 = 31).
A157
PID Sleep Operation
Delay Time
0.0 to 25.5
Set the delay time until sleep operation
is started.
0.0 s
C044
PID Deviation
Excessive Level
0.0 to 100.0
OD signal output judgment level
3.0 %
C052
Feedback Comparison
Signal Off Level
0.0 to 100.0
FBV signal output judgment level
100.0 %
C053
Feedback Comparison
Signal On Level
0.0 to 100.0
FBV signal output judgment level
0.0 %
C001 to C007
Multi-function Input
Selection
23: PID (PID disabled)
−−
24: PIDC (PID integral reset)
C021 to C022
C026
Multi-function Output
Terminal Selection
Multi-function
Relay Output
Function Selection
04: OD (PID excessive deviation)
−−
31: FBV (PID FB status output)
Related functions A001, A005, d004
*1. Refer to "Frequency Operation Function" on page 5-70.
*2. Refer to "Analog Input (FV, FI)" on page 5-37.
Parameter
No.
Function name Data
Default
setting
Unit