6-34
6-8 List of Modbus Communication (Modbus-RTU) Data
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6
Communication Function
0044h Fault Monitor 6: Cause
d086 R
Refer to "Inverter Fault Factor
List" on page 6-35.
−
0045h
Fault Monitor 6:
Inverter Status
Refer to "Inverter Fault Factor
List" on page 6-35.
−
0046h
Fault Monitor 6:
Frequency (HIGH)
0 to 100000 0.01 [Hz]
0047h
Fault Monitor 6:
Frequency (LOW)
0048h
Fault Monitor 6:
Current
Output current value at the
time of tripping
0.01 [A]
0049h
Fault Monitor 6:
Voltage
DC input voltage at the time of
tripping
0.1 [V]
004Ah
Fault Monitor 6: RUN
Time (HIGH)
Total RUN time at the time of
tripping
1 [h]
004Bh
Fault Monitor 6: RUN
Time (LOW)
004Ch
Fault Monitor 6: ON
Time (HIGH)
Power ON time at the time of
tripping
1 [h]
004Dh
Fault Monitor 6: ON
Time (LOW)
004Eh Warning Monitor d090 R Warning code −
004Fh
to
08FFh
Not used −−Inaccessible −
0900h EEPROM Write − W
0: Motor parameter
recalculation
1: Set value storage in
EEPROM
Other: Motor parameter
recalculation and set
value storage in
EEPROM
−
0901h Not used −−Inaccessible −
0902h
EEPROM Write Mode
Selection
− W
0: Write disabled
1: Write enabled
−
0903h
to
1000h
Not used −−Inaccessible −
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting
parameters
Data
resolution