7-5
7-1 Error Display and Remedial Actions
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
7
Maintenance Operations
Brake error A trip will occur if brake ON/OFF cannot
be confirmed within the Brake
Confirmation Wait Time (b124) after the
Inverter has issued a brake release
output, provided that the Brake Control
function is enabled (b120 = 01).
E36.
Is the brake ON/OFF function
working?
Check the brake.
Is the set time for b124 too
short?
Increase b124 .
Has the brake confirmation
signal been input?
Check the wiring.
5-142
Emergency
shutoff
*1
E37.
Overload
protection in a
low speed
range
If an overload occurs in the extremely
low speed range of 0.2 Hz or below, it
will be detected by the built-in
electronic thermal of the Inverter and a
trip will occur. (However, the error
history may indicate a high frequency).
E38.
Is the load too large?
Decrease the load rate.
Poor Digital
Operator
connection
The Inverter is tripped when there is an
error or broken line for communications
with an externally connected Operator
(optional).
E40.
Is there a communications
error?
Check the cable and
replace it if necessary.
This error will not be
detected if b165 is set to
02 (ignore).
5-85
5-86
Modbus
communication
(Modbus-RTU)
error
A trip will occur upon timeout if the
communication error selection is set to
tripping (C076 = 00).
E41.
Is the communication speed
correct?
Check the setting.
Is the wiring distance
appropriate?
Check the
communication wiring.
Has disconnection occurred?
Check the wiring.
6-3
Internal data
error
E43.
to
E59.
Option error
This error is reported by an optional
board.
E60.
to
E68.
Refer to the manual for the
optional board for details.
Option timeout
A timeout occurred in communications
between the Inverter and optional
board, and the Inverter was tripped.
E69.
The optional board is
disconnected.
Check to see if the case
of the optional board is
mating properly with the
Inverter. Tighten the
mounting screws.
The option board is
malfunctioning.
If the optional board is
mated properly, it may have
failed.
Name Description
Error
code
Check point and remedy
Reference
page