EasyManua.ls Logo

Omron CP1E CPU UNIT SOFTWARE - Page 226

Omron CP1E CPU UNIT SOFTWARE
450 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13 PWM Outputs
13-4
CP1E CPU Unit Software User’s Manual(W480)
PLC Setup
There are no settings that need to be made in the PLC Setup.
DM Area Settings
• PWM Operand Settings (D0 and D1)
Ladder Diagram
Preparations
Setting Operand Data
Frequency: 2,000.0 Hz D0 #4E20
Duty factor: 40.0% D1 #0190
@PWM
#1000
D0
D1
#1000
#0003
D10
0.00
0.01
Start input
Stop input
←PWM output 0 (Duty factor in increments of 0.1%, Frequency in increments of 0.1 Hz)
←Frequency setting
←Duty factor setting
←PWM output 0
←Stops pulse output
←Not used.
@INI

Table of Contents