7-3
7 PLC Setup
CP1E CPU Unit Software User’s Manual(W480)
7-2 PLC Setup Settings
7
7-2-1 Startup and CPU Unit Settings
7-2 PLC Setup Settings
7-2-1 Startup and CPU Unit Settings
Startup Data Read Setting
Name Default Possible settings
When setting is read by
CPU Unit
1 Clear Held Memory (HR/DM/CNT) to Zero Do not clear. Do not clear. When power is turned ON
Clear.
2 Read D0- from backup memory Do not read. Do not read. When power is turned ON
Read.
3 Number of CH of DM for backup 0 E-type CPU Unit: 0 to 1,499 When power is turned ON
N/NA-type CPU Unit: 0 to 6,999
Startup Mode Setting
Name Default Possible settings
When setting is read by
CPU Unit
1 Startup Mode Setting Run: RUN mode Program: PROGRAM mode When power is turned ON
Monitor: MONITOR mode
Run: RUN mode
Execute Process Settings
Name Default Possible settings
When setting is read by
CPU Unit
1 Stop CPU on Instruction Error Do not stop. Do not stop. At start of operation
Stop.
2 Don’t register FAL to error log Register. Register. When power is turned ON
Do not register.
3 Do not detect Low Battery
(N/NA-type CPU Unit only)
Do not detect. Do not detect. Every cycle
Detect.
7-2-2 Timing and Interrupt Settings
Timing and Interrupt Settings
Name Default Possible settings
When setting is read by
CPU Unit
1 Watch Cycle Time 1 s Other than initial setting (any) At start of operation
1ms
:
1,000 ms
2 Constant Cycle Time No setting (variable) Setting At start of operation
1ms
:
1,000 ms