Instruction Mnemonic Variations Symbol/Operand Function
TRANSMIT TXD @ Outputs the specified number of bytes of data without conversion
from the RS-232C port built into the CPU Unit or the serial Option
Board according to the start code and end code specified for
no-protocol mode in the PLC Setup.
C: Control word
RECEIVE RXD @ Reads the specified number of bytes of data starting with the
specified first word from the RS-232C port built into the CPU Unit
or the serial Option Board according to the start code and end
code specified for no-protocol mode in the PLC Setup.
C: Control Word
TXD(236)
S
C
N
S: 1st source word
C: Control word
N: Number of bytes
0000 to 0100 hex
(0 to 256 decimal)
15 8 011 37412
C
Always 0
Byte order
0: Most significant bytes first
1: Least significant bytes first
RS and ER signal control
0: No RS and ER signal control
1: RS signal control
2: ER signal control
3: RS and ER signal control
Serial port specifier
1: CPU Unit’s RS-232C port
2: Serial Option Board port
RXD(235)
D
C
N
D: 1st destination word
C: Control word
N: Number of bytes to store
0000 to 0100 hex
(0 to 256 decimal)
C
812 3415 0711
Byte order
0 Hex: Most significant byte
to least significant byte
1 Hex: Lest significant byte
to most significant byte
CS and DR signal monitoring
0: No CS and DR signal monitoring
1: CS signal monitoring
2: DR signal monitoring
3: CS and DR signal monitoring.
Always 0
Serial port specifier
1: CPU Unit’s RS-232C port
2: Serial Option Board port